Campo DC | Valor | Idioma |
dc.creator | Scaramussa Júnior, Marcos Olívio | - |
dc.date.accessioned | 2022-10-07T15:45:38Z | - |
dc.date.available | 2022-10-07T15:45:38Z | - |
dc.date.issued | 2019 | - |
dc.identifier.uri | https://repositorio.ufba.br/handle/ri/36114 | - |
dc.description.abstract | The technical, environmental and economic feasibility of cogeneration systems,
based on natural gas internal combustion engines and absorption chillers was
investigated. Projects that meet the growing demand for diversification of energy
supply in Brazil are already well studied, but the alignment between the modern
incentive and regulation laws with the technologies available in the market for
application in supermarkets are not well understood. The objective of the study was
divided into: development of a technical indicator (AT) and an economic indicator
(VEO) for a general evaluation of cogeneration projects; application of an
environmental indicator; mapping constraints and project requirements with respect
to the legislation of qualified cogeneration and energy compensation; electrical and
thermal load survey in a case study; modeling of the cogeneration plant to meet the
case study; evaluation of the case study using the indicators developed. The results
present the best combinations for the implementation of cogeneration systems,
through a technical approach, using different absorption chiller models; and an
environmental approach, with the emission of CO2 from these systems, compared
to the emission of the Brazilian matrix. In the economic aspect, the results show the
feasibility of implementing the model in a supermarket, together with the daily
projection of energy billing and an investments analysis in three risk scenarios. The
model showed that the proposed system is technically and financially viable in all
scenarios. In the first scenario, with the system running 14 hours a day, the VEO
and NPV were positive, the IRR was 4.4% a.m. and a payback of 3.6 years. In the
second scenario, with the model operating 24 hours a day, VEO and NPV remained
positive, with the IRR at 6.5% a.m. and a payback of 2.6 years. For the third
scenario, with the model being aided by a thermal reservoir to accumulate cold
water, all investment indicators remained favorable, with VEO and NPV positive,
IRR at 4.2% a.m. and payback at 3.7 years. | pt_BR |
dc.language | por | pt_BR |
dc.publisher | Universidade Federal da Bahia | pt_BR |
dc.subject | Cogeração (energia) | pt_BR |
dc.subject | Motor de combustão interna | pt_BR |
dc.subject | Refrigeração por absorção | pt_BR |
dc.subject | Gás natural | pt_BR |
dc.subject | Geração distribuída (energia) | pt_BR |
dc.subject | Supermercado | pt_BR |
dc.subject | Salvador (BA) | pt_BR |
dc.subject.other | Cogeneration (energy) | pt_BR |
dc.subject.other | Internal combustion engine | pt_BR |
dc.subject.other | Absorption chiller | pt_BR |
dc.subject.other | Natural gas | pt_BR |
dc.subject.other | Distributed generation (energy) | pt_BR |
dc.subject.other | Supermarket | pt_BR |
dc.subject.other | Salvador (BA) | pt_BR |
dc.title | Sistemas de cogeração para pequenas e médias empresas do setor terciário | pt_BR |
dc.type | Dissertação | pt_BR |
dc.contributor.referees | Ferreira, Vitor Pinheiro | - |
dc.publisher.program | Programa de Pós-Graduação em Engenharia Industrial (PEI) | pt_BR |
dc.publisher.initials | UFBA | pt_BR |
dc.publisher.country | Brasil | pt_BR |
dc.subject.cnpq | CNPQ::ENGENHARIAS | pt_BR |
dc.contributor.advisor1 | Torres, Ednildo Andrade | - |
dc.contributor.advisor2 | Silva, Julio Augusto Mendes da | - |
dc.contributor.referee1 | Torres, Ednildo Andrade | - |
dc.contributor.referee2 | Silva, Julio Augusto Mendes da | - |
dc.contributor.referee3 | Almeida, Antonio Gabriel Souza | - |
dc.creator.Lattes | http://lattes.cnpq.br/6404867456336336 | pt_BR |
dc.description.resumo | A viabilidade técnica, ambiental e econômica de sistemas de cogeração de energia,
baseados em motor alternativo a gás natural e chiller por absorção foi investigada.
Projetos que atendam à crescente demanda por diversificação da oferta energética
no Brasil já são bem estudados, mas o alinhamento entre as modernas legislações
de incentivo e regulação com as tecnologias disponíveis no mercado para aplicação
em supermercados não é bem compreendido. O objetivo do estudo foi dividido em:
desenvolvimento de um indicador técnico (AT) e um indicador econômico (VEO)
para avaliação geral de projetos de cogeração; aplicação de um indicador
ambiental; mapeamento das restrições e exigências de projeto no que diz respeito
à legislação da cogeração qualificada e compensação de energia; levantamento da
carga térmica e elétrica em um estudo de caso; modelagem da planta de cogeração
para atender o estudo de caso; avaliação do estudo de caso por meio dos
indicadores desenvolvidos. Os resultados apresentam as melhores combinações
para implantação de sistemas de cogeração, através de uma abordagem técnica,
utilizando diferentes modelos de chiller por absorção; e uma abordagem ambiental,
com a emissão de CO2 desses sistemas, comparada com a emissão da matriz
brasileira. No quesito econômico, os resultados apresentam a viabilidade de
implantação do modelo em um supermercado, junto com a projeção diária do
faturamento da energia e uma análise de investimentos em três cenários de risco.
O modelo mostrou que o sistema proposto é tecnicamente e financeiramente viável
em todos os cenários. No 1º cenário, com o sistema funcionando 14 horas por dia,
o VEO e o VPL foram positivos, a TIR ficou em 4,4% a.m. e um payback de 3,6
anos. No 2º cenário, com o modelo operando 24 horas por dia, o VEO e o VPL
continuaram positivos, com a TIR em 6,5% a.m. e um payback de 2,6 anos. Para o
3º cenário, com o modelo sendo auxiliado por um reservatório térmico para
acumular água gelada, todos os indicadores de investimentos continuaram
favoráveis, com VEO e VPL positivos, TIR em 4,2% a.m. e payback de 3,7 anos. | pt_BR |
dc.publisher.department | Escola Politécnica | pt_BR |
dc.type.degree | Mestrado Acadêmico | pt_BR |
Aparece nas coleções: | Dissertação (PEI)
|